American Journal of Electrical and Electronic Engineering. 2017, 5(4), 159-165
DOI: 10.12691/AJEEE-5-4-6
Original Research

Load Flow Assessment of the Nigeria 330-kV Power System

Ignatius K. Okakwu1, , Emmanuel A. Ogujor1 and Patrick A. Oriaifo1

1Department of Electrical/Electronic Engineering, Faculty of Engineering, University of Benin, Benin City, Nigeria

Pub. Date: August 03, 2017

Cite this paper

Ignatius K. Okakwu, Emmanuel A. Ogujor and Patrick A. Oriaifo. Load Flow Assessment of the Nigeria 330-kV Power System. American Journal of Electrical and Electronic Engineering. 2017; 5(4):159-165. doi: 10.12691/AJEEE-5-4-6

Abstract

The Nigerian 330kV grid network is characterized with major problems like voltage instability (voltage profile violation), long transmission lines, nature of transmission lines and high power losses which affect power generation and distribution systems. This paper considered the load-flow study of the Nigerian 330-kV consisting of 32 buses, 11 generating stations and 36 transmission lines. Newton-Raphson iteration technique was used to carry out the analysis because of its fast convergence nature as compared to other iterative techniques. The data used for the study is obtained from Power Holding Company of Nigeria (PHCN). MATLAB/SIMULINK software was used to carry out the simulations. The results obtained shows that some of the bus voltages lie outside the prescribed limit of 0.95-1.05 pu (313.5 – 346.5kV). These buses include buses 16 (Kano 0.8721pu), 17(Kaduna, 0.9046pu), 18(Jos, 0.8580pu), 19(Gombe 0.8735pu) and 21(Katampe, 0.9167pu). The total active power loss is 268.622MW and that of reactive power loss is 2247.42Mvar. It is therefore inferred from the results obtained that the existing Nigerian 330-kV grid network is fraught with high line losses that require compensation using reactive power supports such as Flexible Alternating Current Transmission Systems (FACTS) devices, for effective line utilization.

Keywords

load flow, Newton Raphson, losses, voltage, transmission line

Copyright

Creative CommonsThis work is licensed under a Creative Commons Attribution 4.0 International License. To view a copy of this license, visit http://creativecommons.org/licenses/by/4.0/

References

[1]  Omorogiuwa Eseosa and Emmanuel A. Ogujor. Determination of bus voltages, power losses and flows in the Nigeria 330kV integrated power system. International Journal of Advances in Engineering and Technology. 2012; 4: 94-106.
 
[2]  Akintunde S. Alayande, Adisa A. Jimoh and Adedayo A. Yusuff. Voltage profiles and loss reduction in weak meshed network. Proceedings of the IASTED International Conference, Power and Energy System. 2014; 220-226.
 
[3]  Nagesh H. and Puttaswanmy P. Enhancement of voltage stability Margin using FACTS Controllers. International Journal of Computer and Electrical Engineering. 2013; 5:161-265.
 
[4]  Izuegbunam F., Duruibe S. and Ojukwu G. Power Flow Contingency Assessment Simulation of the expanded 330kV Nigeria Grid using Power World Simulator. Journal of Emerging Trends in Engineering and Applied Sciences. 2011; 2:1002-1008.
 
[5]  Aribi, F., Nwohu M., Sadiq A. and Ambafi J. Voltage profile enhancement of the Nigerian North-East 330kV Power Network using STATCOM. International Journal of Advanced Research in Science, Engineering and Technology. 2015; 2:330-337.
 
[6]  Ademola A., Awosope C., Samuel I. and Agbetuyi A. Contingency Analysis for assessing line losses in Nigeria 330kV power lines. 2016; 5: 66-78.
 
[7]  Jokojeje R., Adejumobi I., Mustapha A. and Adebisi O. Application of STATCOM in improving power station performance: A Case Study of the Nigeria 330kV Electricity Grid. Nigerian Advanced Journal of Technology (NIJOTECH). 2015; 34: 564-572.
 
[8]  Mashauri A. Load Flow Solution of the Tanzania power network using Newton-Raphson method and MATLAB software. International Journal of Energy and Power Engineering. 2014; 277-286.